Thermal Mass Gas Flowmeter

Thermal Mass Gas Flowmeter
نظرة عامة

Direct mass-flow measurement of gases with no moving parts and negligible pressure loss. Inline meters from ¼" to 2" and insertion probes for 2½" to 99" pipes and ducts, to 69 bar and 454 °C, with HART, fieldbus, Modbus and in-situ calibration verification.

Size¼"–2" inline; 2½"–99" insertion type
Connection typethreaded / flanged / retractable / fixed welded
Measuring rangemodel-dependent; 0.01–950 Nm³/h or 0.07–305 Nm³/h
Process pressureup to 69 bar
المواصفات الفنية

Thermal Mass Gas Flowmeter

Size¼"–2" inline; 2½"–99" insertion type
Connection typethreaded / flanged / retractable / fixed welded
Measuring rangemodel-dependent; 0.01–950 Nm³/h or 0.07–305 Nm³/h
Process pressureup to 69 bar
Process temperature−40 to +454 °C
Wetted parts material316 stainless steel / Hastelloy
Outputs and communications4–20 mA + HART® / RS-485 / FOUNDATION™ Fieldbus H1 / PROFIBUS PA / frequency or pulse / USB / Ethernet
Accessorieslocal LCD display, flow conditioner, in-situ calibration verification, dual-element configuration, data logger, stainless-steel housing
Applicationdirect gas mass-flow measurement, fuel-gas lines, burners and boilers, compressed air, dosing, injection, sub-metering
Industryonshore and offshore oil and gas, refining, petrochemical, chemical, power generation, HVAC, emissions monitoring
التفاصيل

A thermal mass flowmeter has two temperature sensors in the gas stream; one is heated, and the power needed to hold a constant temperature difference between them is a direct function of the mass of gas passing. Because the measurement responds to mass rather than volume, no pressure or temperature compensation is required, and the meter keeps its accuracy at the low flows and low pressures where orifice plates and vortex meters give up.

Inline models from ¼" to 2" suit small lines such as burner fuel gas, purge and blanketing gas, dosing and sub-metering. Insertion models cover 2½" to 99" pipes and ducts with threaded, flanged, fixed-welded or retractable mounting, the last allowing removal under pressure. Ranges are model-dependent, from 0.01 to 950 Nm³/h and 0.07 to 305 Nm³/h, at pressures to 69 bar and temperatures from −40 to +454 °C. Wetted parts are 316 stainless steel or Hastelloy.

Communication options include 4–20 mA HART, RS-485, FOUNDATION Fieldbus H1, PROFIBUS PA, frequency or pulse, USB and Ethernet. A local LCD, flow conditioner, dual-element configuration for redundancy, data logger and in-situ calibration verification are available, the last documenting sensor health without removing the meter from the line.

Users are onshore and offshore oil and gas, refining, petrochemical, chemical, power, HVAC and emissions monitoring, including compressed-air audits and boiler air-fuel ratio control.